Storage tank general precautions

Sep 04, 2019

Leave a message

Storage tank general precautions

The oil storage tanks and storage tanks have a large amount of oil, which is dangerous and prone to fires and explosions. It is necessary to establish a fire prevention and explosion prevention system in accordance with relevant regulations, conduct regular fire inspections, and strictly carry out fire safety management to ensure fire safety.

(1) Fire and explosion protection of oil storage tanks and storage tanks shall be in accordance with GB50183 and GB50074. Low-fold air foam fire extinguishing system shall be in accordance with GB50151.

(2) The storage tank area should be kept clean and tidy. There should be no hay, no oil and no combustibles in the fireproof embankment.

(3) The drainage system of the storage tank area shall be provided with a water-sealed well; the drainage pipe shall be provided with a valve outside the fire protection levee; when the oil tank is discharged, special personnel shall be inspected to remove the residual oil in the water-sealed well in time.

(4) Non-explosion-proof electrical equipment and high-voltage overhead lines shall not be installed in the tank area.

(5) The storage tank area shall be provided with fireproof dams as required, and the fireproof dykes shall be kept intact.

(6) The top of the oil storage tank should be free from oil and water. Insulation measures should be taken for oil storage tanks to enter and exit oil pipelines and valves.

(7) The light-transparent hole, the metering hole cover and the gasket on the top of the oil storage tank should be kept intact, and the hole cover should be tightly covered. The fuel port should be equipped with a metal gasket that does not spark.

(8) The fire alarm valve and the hydraulic safety valve base on the oil storage tank should be equipped with a flame arrester. The flame arrester is inspected at least once a quarter.

(9) The toughness hose compensator shall be installed in the oil inlet and outlet of the oil storage tank.

(10) The steel storage tank body shall be provided with lightning protection and anti-static grounding device, and its grounding resistance shall not exceed 10Ω. The grounding point should be set at least one place every 30m along the bottom of the tank, and the grounding of the single tank should be no less than two.